9
the SLC loop and can be placed up to 10,000 feet from the control or
5815XL SLC loop module.
2.1.8 Annunciators
A. The main control shall have a built in annunciator with an 80-character
LCD display and feature LED’s for General Alarm, Supervisory, System
Trouble, System Silence and Power. When in the normal condition the
LCD shall display time and date based on a 200 year clock which is capable
of automatic daylight savings time adjustments. All controls and
programming keys are silicone mechanical type with tactile and audible
feedback. Keys shall have a travel of .040 inches. No membrane style
buttons shall be permissible. The annunciator shall be able to silence and
reset alarms through the use of a keypad entered code or by using a
firefighter’s key. The annunciators shall have twenty levels of user codes
that shall allow the limitation of operating system programming to
authorized individuals.
2.1.9 Remote Annunciators
A. The fire system shall be capable of supporting up to eight (8) remote LCD
annunciators, Model 5860, and eight (8) LED remote annunciators, Model
5865. LCD remote annunciators shall have the same control and display
layout so that they match identically the built-in annunciator. LED remote
annunciators shall have individually mapped LEDs and reset and silence
inputs. The reset and silence inputs shall use the same firefighter’s key as
the LCD annunciators. Remote annunciators shall be capable of operating
at a distance of 6,000 feet from the main control panel on unshielded, non-
twisted cable.
2.1.10 I/O Module
A. The fire system shall be able to support up to eight (8) I/O modules, Model
5880, which shall be used to drive remote LED graphic style displays and
accommodate up to eight dry contact type switch inputs. The I/O modules
shall each drive up to 40 LEDs without requiring external power
connections. The I/O module inputs shall be supervised and be suitable for
alarm and trouble circuits as well as reset and silence switches.
2.1.11 Serial/Parallel Interface
A. The fire system shall be capable of supporting up to two (2) serial / parallel
interface modules, Model 5824, that are capable of driving standard
computer style printers. The interface shall be programmable as to what
information is sent to it and shall include the ability to print out detector
status by point, event history by point, and system programming.