D. A bypass mode shall allow for any point or NAC circuit to be bypassed
without affecting the operation of the total fire alarm system.
2.1.18 Remote Input Capabilities
A. The control panel shall have provisions for supervised switch inputs for the
purpose of alarm reset, and alarm and trouble restore.
2.1.19 Notification Appliance Mapping Structure
A. All notification circuits and modules shall be programmable via a mapping
structure that allows for a maximum of 250 output groups. Each of these
groups shall have the ability to be triggered by any of the panel’s 125 zones.
A zone may trigger groups individually or may contain a global trigger for
manual pull stations, fire drills and two different system alarms.
Additionally, each zone shall individually control the cadence pattern of
each of the groups that it is “mapped” to so that sounders can indicate a
variety of conditions. The zone shall be capable of issuing a diffe
rent
cadence pattern for each of the groups under its control. The mapping
structure shall also allow a group to be designated to “ignore cadencefor
use with strobes and other continuous input devices. Zones shall have eight
different output categories; Detector Alarm, Trouble, Supervisory, Pre-
Alarm, Waterflow, Manual pull, Zone Auxiliary 1 and Zone Auxiliary 2.
Each of the categories shall have the ability to control from 1 to 8 output
groups with a cadence pattern. The patterns are; March Code, ANSI S-
3.41, Single Stroke Bell Temporal, California Code, Zone 1 Coded, Zone 2
Coded, Zone 3 Coded, Zone 4 Coded, Zone 5 Coded, Zone 6 Coded, Zone
7 Coded, Zone 8 Coded, Custom Output Pattern 1, Custom Output Pattern
2, Custom Output Pattern 3, Custom Output Pattern 4, Constant, ANSI 4
Temporal, Amseco Synchronization, Faraday Synchronization, Gentex
Synchronization, System Sensor Synchronization and Wheelock
Synchronization. This mapping/cadence pattern shall be supported by all
system power supplies and notification expander modules.
2.1.20 On-Board Programmer
A. The FACP shall have an on board programmer which shall allow for all
system functions and options to be programmed via the on board
annunciator keypad. Any panel that does not have this capability shall not
be accepted.
2.1.21 Downloading Software
A. The fire alarm control panel shall support up/downloading of system
programming from a PC under Windows XP, Windows Vista, or Windows
7. The FACP shall also be able to download the detector sensitivity test
results and a 1000 event system event buffer to the PC. Communication
shall take place over a direct connection to the PC and/or via the same
telephone lines as the built in digital communicator and shall not require an
external modem to be connected to the panel. The downloading software