7. The FACP shall have a built-in UL approved digital communicator
which shall allow local and remote up/downloading of system
operating options, event history, and detector sensitivity data.
8. The FACP shall automatically test the smoke detectors in
compliance with NFPA standards to ensure that they are within
listed sensitivity parameters and be listed with Underwriters
Laboratories for this purpose.
9. The FACP shall compensate for the accumulation of contaminants
that affect detector sensitivity. The FACP shall have day/night
sensitivity adjustments, maintenance alert feature (differentiated
from trouble condition), detector sensitivity selection, auto-
programming mode (Jumpstart) and the ability to upgrade the core
operating software on site or over the telephone.
10. The FACP shall have maintenance alert feature (differentiated from
trouble condition) and a calibration trouble condition.
11. The FACP shall have a jumpstart feature that can automatically
enroll all properly connected accessories into a functional system
within 60 seconds of powering up the panel. Panels that do not
have these capabilities shall not be accepted.
12. The main communication bus (SBUS RS485) shall be capable of
class A or class B configuration with a total bus length of 6,000
feet.
2.1.2 System Wiring
A. The Signaling Line Circuit (SLC) and data communication bus (SBUS)
shall be wired with standard NEC 760 compliant wiring. No twisted,
shielded or mid-capacitance wiring is permitted for standard installations.
All FACP screw terminals shall be capable of accepting 14-18 AWG wire.
All system wiring shall be in accordance with the requirements of NFPA
70, the National Electrical Code (NEC) and also comply with article 760 of
the NEC.
2.1.3 Signaling Line Circuits
A. Each SLC shall be capable of a wiring distance of 10,000 feet from the SLC
driver module (5815XL) and be capable of supporting 99 detectors and 99
addressable module devices. The communication protocol to SLC devices
shall be digital. Any SLC loop device which goes into alarm shall interrupt
the polling cycle for priority response from the FACP. The FACP shall
respond consistently to a device that goes into alarm on an SLC within ten
(10) seconds. The auxiliary 5815XL SLC loop module shall be capable of
being located up to 6,000 feet from the FACP on the SBUS, which is