Model 4821/4820 Control/Communicator Installation Manual
6-24 150966
Alarm Delay
Mode
Use this option to select the type of delay (if any) the zone will have. Options are: No Delay
No delay
The zone will cause alarms immediately.
Entry delay
A zone selected as an entry delay zone will begin an entry countdown when an alarm is
tripped. The alarm tones and reporting will be delayed until the entry delay timer reaches 0
or the user acknowledges it by entering a valid code to disarm the area.
Entry delay follower
Interior zone annunciations and reports will be delayed when an entry zone is violated.
Cross alarm delay
When an alarm occurs in a cross alarm zone, an audible warning tone will sound on the
internal 1 speaker and all Touchpads in the area, but an alarm will not be reported unless
another zone in the same area also goes into alarm.
The cross alarm delay is reset when a user acknowledges it by entering a code. Cross alarm
delay events are stored in the event history buffer.
Smoke verification delay
If an alarm occurs in a zone selected as smoke verify, the panel will not automatically go
into alarm unless the zone is tripped a second time during the smoke verification cycle. See
Section 4.16.1.2 for more information.
Note: Do not select the 10 second response speed if you are using this option.
Entry Delay Enter the duration (number of seconds) for the entry delay. Entry delay must be enabled in
order for the duration to take effect (see previous option). In a UL installation, the duration
of the delay must not be longer than 45 seconds.
0
Interior The 4821/4820 can have two groups of interior zones which can be controlled separately
through the key. Use this option to assign zones to Interior 1 or Interior 2.
Options for assigning zones are:
None (no interior zones)
Interior 1 (first group of interior zones)
Interior 2 (second group of interior zones)
None
Bypassable
Zone
If this option is enabled, the zone can be bypassed. Do not select for fire zones. Enabled
**Silent
Alarm
If this option is enabled, alarm conditions will not be annunciated at any speaker or
touchpad but will report to the central station. This option has precedence over all audibles,
including the “Bell if dialer fails” option (see below).
Disabled
**Invisible
Alarm
If this option is enabled, alarm conditions and dialer activity will not display at any
touchpad but alarm conditions will report to the central station.
Disabled
Delay
Reporting
If this option is enabled, reporting alarm events for this zone will be delayed by the amount
of time programmed in the partition options.
Disabled
Table 6-7: Zones Screen Options and Descriptions