Series 5000 Entry System Installation/Operation Manual
3-12 151174
Wiring Distance calculation example:
Suppose a system is configured as follows:
1 - 5083 as the Master unit.
2 - 5083 satellite units
The total worst case current is calculated as follows:
Using this value, and referring to the Wiring Distance table, it can be found that the available
options are:
154 feet maximum using 22 Gauge wire
391 feet maximum using 18 Gauge wire
622 feet maximum using 16 Gauge wire
984 feet maximum using 14 Gauge wire
Two 5083 satellite units = 2 x .200 amps = .400 amps
Total Worst Case Current Draw = .400 amps