Installation
P/N 151253 19
4.10.3 Setting the Loss of AC Delay
Normal selection for reporting loss of AC is 6 hours.
The ON position is for test purposes only and the normal position for Switch 4 is OFF. For
testing the Low AC reporting, you can temporarily turn Switch 4 ON without removing
power.
Note:Remember to turn the switch OFF when testing is complete.
Figure 4-15 Setting DIP Switch 4
4.10.4 Setting the Auxiliary Output
Switch 5 on the DIP switch determines how the auxiliary power operates on the 5499.
The 5499 checks switch 5 only when powering up the 5499. If you change this switch, you
must remove both the AC power and the battery to force the 5499 to recognize the new switch
setting.
Figure 4-16 Setting DIP Switch 5