Sample Applications
P/N 151253 27
6.3 Door Holder Application
In a typical door holder application, the door holder power must be interrupted to close all fire
doors under the following conditions:
Any active alarm condition.
AC power is no longer present (to conserve battery power).
To close the fire doors in these situations, wire an N.C. programmable relay from the fire
panel in series with the auxiliary power to the door holders as shown in Figure 6-7.
The circuit shown in Figure 6-7 will provide up to 3 amps of door holder power. (See Section
6.2 if you need more than 3 amps of auxiliary power.) The power in this example is released
when AC power is off for 30 seconds or more, or when the relay from the fire panel becomes
open. You would have to use the equivalent of a programmable relay from a fire alarm control
panel that is programmed to transfer under alarm conditions. See Section 4.10.4 for selecting
auxiliary power options.
Figure 6-7 Door Holder Wiring Example
5499
Fire Panel
ESL DHX 1224