Model 5700 Installation and Operation Manual
4-4 151295
4.3 Battery Connection
The control panel battery charge capacity is 7.0 to 35 AH. The main control cabinet can house
batteries up to 7 AH, larger capacity batteries can be housed in a Remote Battery Box (P/N
RBB). See Section 4.3.1 for deteails.Use 12V batteries of the same AH rating. Determine the
correct AH rating as per your current load calculation (see Section 3.6).
Maximum battery charging current 3.1 Amps.
Wire batteries in series to produce a 24-volt equivalent. Do not parallel batteries to increase
the AH rating.
The following steps and diagram explain how to connect the batteries.
1. Connect the black wire from the control panel negative (–) battery terminal to the negative
(–) side of Battery #2.
2. Connect the jumper wire provided (P/N 140694) from the positive (+) side of Battery #2
to the (–) negative side of Battery #1.
3. Connect the red wire from the control panel positive (+) terminal to the positive (+) side of
Battery #1.
Figure 4-3 Battery Connection
Red
Black
Battery Jumper
(P/N 140694)
Shipped With Panel
UL Listed 12V Battery
UL Listed 12V Battery
Battery 2
Battery 1
Supervised