Model 5700 Installation and Operation Manual
6-2 151295
6.1.1 Input Points
JumpStart will determine the number and type of input points (detectors or contact monitor
modules) on each SLC loop. JumpStart assigns the correct detector type (heat, or
photoelectric), so the installer does not need to edit device type for detectors. Any contact
monitor modules on the system will be assigned type "Manual Pull." The installer will need to
manually change the switch type if manual pull is not correct.
JumpStart creates one zone (Zone 1) and assigns all input points to Zone 1. Zone 1 is mapped
to Output Group 1. After JumpStart completes, you can re-map to configure a multiple zone/
output group system (see Section 7.3.1.3). For a general explanation of mapping, see Section
6.2.
6.1.2 Output Points
JumpStart creates three output groups and assigns output circuits as follows:
Circuits 1-2:
Configured as Notification and assigned to Group 1. JumpStart automatically programs Zone
1 to activate Group 1 using constant on output.
Circuit 3 (Relay 1):
Assigned to Group 124. JumpStart automatically programs Zone 1 to activate Group 124
using constant on output when a supervisory condition occurs.
Circuit 4 (Relay 2):
Assigned to Group 125. JumpStart automatically programs Zone 1 to activate Group 125
using constant on output when an alarm occurs.
Addressable output points (Relay modules):
All addressable relay devices will be configured as "Output Pt" (general purpose output point)
and assigned to Group 1.
Note: Relay output is constant even if the zone activating the relay is programmed with an output pattern.
6.1.3 Running JumpStart
Run JumpStart immediately after addressing and connecting all input devices (detectors, pull
stations, and so on) and output devices (notification appliances, relays, and so on).
Note: To install a few devices manually after running JumpStart, see Section 7.
To run JumpStart:
1. Press to view the Main Menu.
2. Select for Program Menu.
3. From the next menu, select for JumpStart.
4. When the message "WARNING Will DELETE all system options" displays, select Yes. A
series of messages displays for the next several seconds. JumpStart scans the SLC loops
for devices and can take several minutes, depending on the number of devices attached.