Programming
151295 7-5
8. Select the characters for the zone name by pressing the or arrow until the desired
character is shown then press .
OR
Enter the Numerical Designator for the character you want, then press . See Appendix B
Table B-1 of this manual for a list of available characters and their numeric designators.
9. Repeat step 8 until the name is complete.
10. Press when the name is complete.
7.3.1.2 Edit Zone Properties
Zone properties consist of, alarm delay characteristics, and heat detector sensitivity.
1. Do steps 1 through 6 of Section 7.3.1.
2. Press to edit the properties of the selected zone.
2
Detection type also selected from
this screen (see Table 7-1).