Seitenansicht 55
Model 5700 Installation and Operation Manual
4-28 151295
4.12.1.2 Class A Notification Wiring
You must use an appliance from the list of compatible appliances in the Appendix at the back
of this manual.
To install a Class A notification appliance circuit:
1. Wire the Class A notification appliances as shown in Figure 4-30.
2. Configure the circuit for Class A in programming (see Section 7.5).
Figure 4-30 Class A Notification Appliance Circuit Configuration
Caution
For proper system supervision do not use looped wire under terminals marked – and + of the Flexput connectors.
Break wire runs to provide supervision of connections.
Supervised
Power Limited
Seitenansicht 55