Installation andOperations ManualPart Number 151295 Rev E11/2006Addressable Fire Control PanelINTELLIKNIGHTMODEL 5700
Model 5700 Installation and Operation Manualvi 151295Section 11Installation Records ...
Model 5700 Installation and Operation Manual7-8 151295To map zone events to outputs, follow these steps:1. From the Main Menu, select for Program Me
Programming151295 7-9Example or Zone Mapping:Suppose you want to program Zone 1 so that:• Any alarm (detector, water flow or manual pull) would activa
Model 5700 Installation and Operation Manual7-10 1512957.3.1.4 Cadence PatternsThe cadence patterns shown in Figure 7-5 are available for use with the
Programming151295 7-117.3.2 Add ZoneTo add a zone, follow these steps:1. Press or to display the main menu.2. Enter the installer code if requested
Model 5700 Installation and Operation Manual7-12 1512957.3.4 View Zone PointsTo view the points in a zone, follow these steps:1. Press or to displa
Programming151295 7-137.4 GroupAn output group is made up of output points that have been programmed to respond in the same way. Output groups simplif
Model 5700 Installation and Operation Manual7-14 1512958. Select the characters for the group name by pressing the or arrow until the desired char
Programming151295 7-15Silencing OptionsThe following silencing options are available for each output group.Response with System-Wide ConditionsYou can
Model 5700 Installation and Operation Manual7-16 15129513. Press the or arrows to select the desired latching option.14. Press .15. Press the or
Programming151295 7-177.4.3 Delete Group1. Press or to display the main menu.2. Enter the installer code if requested.3. Select for Program Menu
151295 1-1Section 1IntroductionThe 5700 Fire Alarm Control / Communicator is an addressable fire control system that meets the requirements of UL 864.
Model 5700 Installation and Operation Manual7-18 1512957.4.5 Edit Output Group TemplatesSome installations may require that zones be mapped to more th
Programming151295 7-197.5 PointYou may need to change characteristics of individual input points (detectors and switches) even after using JumpStart.
Model 5700 Installation and Operation Manual7-20 1512959. Select the type of device by pressing the or arrows. Refer to Table 7-4 under column hea
Programming151295 7-21SLC Loop(cont.)SWITCH(cont.)RESETSystem-level switch provides an alternate way to reset the system; same effect as pressing the
Model 5700 Installation and Operation Manual7-22 1512957.5.2 Point Programming For Internalor External Power Module (5496)To program for an internal o
Programming151295 7-2316. Repeat Steps 1 through 15 for all circuits.7.5.3 Point Programming For 5880 and 5865 ModulesTo program for a 5880 or 5865 mo
Model 5700 Installation and Operation Manual7-24 15129510. Press .11. Press the or arrows to select the desired Group.12. Press .13. Edit module n
Programming151295 7-257.6 System OptionsThis section of the manual explains how to customize software options that affect general operation of the sys
Model 5700 Installation and Operation Manual7-26 1512957.6.1.1 Edit Accounts6. From the next menu, select for Edit Account.A screen similar to one s
Programming151295 7-27Events to ReportThe next six options select which types of events (or event families) will be reported to this account. (See Fig
Model 5700 Installation and Operation Manual1-2 1512951.1.2 Software Features • Advanced smoke detector features:–Automatic drift compensation–Mainten
Model 5700 Installation and Operation Manual7-28 151295The following special characters are available:Use the number buttons on the annunciator or the
Programming151295 7-295. Select for the phone lines menu.6. Select the phone line to be edited (1 or 2) by pressing the or arrow, then press .F
Model 5700 Installation and Operation Manual7-30 1512957.6.2.3 Dial Option (TouchTone or Pulse)9. Press the or arrow to select the dial option, th
Programming151295 7-317.6.2.7 Answering Machine BypassThis option is used in conjunction with the Silent Knight Software Suite 5660. This feature ensu
Model 5700 Installation and Operation Manual7-32 1512957.6.3.1 Trouble EventsYou can map certain system trouble events to an output group. To access t
Programming151295 7-337.6.3.2 System Alarm CadenceFire drill and system auxiliary alarm events can have special cadence patterns to distinguish them f
Model 5700 Installation and Operation Manual7-34 1512957.6.4 Miscellaneous Options 1Through this programming option you can set the water flow delay t
Programming151295 7-357.6.4.2 Low AC Report DelayNote: You must select 1-3 hours in UL central station installations and UL remote signaling installat
Model 5700 Installation and Operation Manual7-36 1512957.6.5 Miscellaneous Options 2Through this programming option you can turn the strobe synchroniz
Programming151295 7-377.6.6 Miscellaneous Options 3From Miscellaneous Options 3, you set the alarm verification time and set the start and end week an
Introduction151295 1-31.3 Compatible ProductsThe chart below lists the products available from Silent Knight for use with the 5700.Note: 5865-3, 5865-
Model 5700 Installation and Operation Manual7-38 1512957.6.7 Edit Banner MessageThe banner is the message that displays on the panel LCD when the syst
Programming151295 7-397.7 JumpStart AutoprogrammingTo run JumpStart:1. Press or to display the main menu.2. Enter the installer code if requested.
Model 5700 Installation and Operation Manual7-40 1512957.8 Computer AccountAn installer at the panel site can initiate communications between the pane
Programming151295 7-417.9 Access CodesAccess codes provide the user access to the control panel functions. Each access code can be customized for each
Model 5700 Installation and Operation Manual7-42 151295To change an access code:1. Press or to display the main menu.2. Enter the installer code i
151295 8-1Section 8System OperationOperation of the control panel is simple. Menus guide you step-by-step through operations. This section of the manu
Model 5700 Installation and Operation Manual8-2 1512958.1.2 BannerThe banner is the message that displays on the control panel when the system is in n
System Operation151295 8-38.2.1 Main Menu OverviewThe chart below is a brief overview of the Main Menu. These options are described in greater detail
Model 5700 Installation and Operation Manual8-4 1512958.3.2 Disable / Enable a Point1. From the Main Menu, select for Point Functions. 2. Select f
System Operation151295 8-58.3.5 Conduct an Indicator TestThe indicator test checks the annunciator LEDs, PZT, and LCD display.1. From the Main Menu, p
Model 5700 Installation and Operation Manual1-4 151295Limitations of Fire Alarm SystemsManufacturer recommends that smoke and/or heat detectors be loc
Model 5700 Installation and Operation Manual8-6 1512958.3.7 Conduct a Dialer Test1. From the Main Menu, press for System Tests.2. Select for Diale
System Operation151295 8-75. A screen similar to those shown in Figure 8-3 will display.Figure 8-3 Checking Detector Sensitivity ComplianceIf a print
Model 5700 Installation and Operation Manual8-8 1512958.3.15 Communicating with a Remote ComputerAn installer at the panel site can initiate communica
System Operation151295 8-98.3.16 Working with a PrinterIf you are using the Model 5824 Serial/Parallel Interface, several printing options are availab
Model 5700 Installation and Operation Manual8-10 1512958.4 Operation Mode BehaviorThe control panel can be in one of seven conditions at any given mom
System Operation151295 8-11Trouble A system trouble condition occurs.The dialer seizes control of the phone line and calls the central station.The on-
Model 5700 Installation and Operation Manual8-12 1512958.5 Releasing OperationsThis control panel supports two types of releasing, Double Interlock Zo
System Operation151295 8-138.5.1 Single Interlock Zone ReleasingA single interlock zone utilizes a minimum of two addressable detectors, and a designa
Model 5700 Installation and Operation Manual8-14 1512958.5.2 Double Interlock Zone ReleasingA Double Interlock Zone uses a minimum of two Addressable
System Operation151295 8-158.6 Smoke Alarm VerificationFigure 8-5 illustrates how the Smoke Alarm Verification cycle operates.Figure 8-5 Smoke Verifi
Introduction151295 1-5• Warning devices (including horns, sirens, and bells) may not alert people or wake up sleepers who are located on the other sid
Model 5700 Installation and Operation Manual8-16 151295
151295 9-1Section 9ReportingThis section lists receivers that are compatible with this control panel, and the reporting codes sent by the control pane
Model 5700 Installation and Operation Manual9-2 151295Local programming aborted or ended with errors Trouble System Event LU 1 628 00 000Periodic test
Reporting151295 9-3Supervisory condition restore Trouble Zone Event SR Zone 3 203 00 ZoneSupervisory condition Trouble Zone Event SS Zone 1 203 00 Zon
Model 5700 Installation and Operation Manual9-4 151295Water flow switch alarm Alarm Point Event pi Exp. ID SA Pnt # 1 113 Exp. ID Pnt #Water flow swit
151295 10-1Section 10Testing and Troubleshooting10.1 TroubleshootingThis section of the manual offers suggestions for troubleshooting hardware problem
Model 5700 Installation and Operation Manual10-2 15129510.2.1 Event HistoryThe event history can be useful for tracking or recalling a trouble conditi
Testing and Troubleshooting151295 10-310.3 Built-in Troubleshooting and Testing ToolsThe fire control panel has several built-in testing and troublesh
Model 5700 Installation and Operation Manual10-4 15129510.3.2 SLC Multi LocatorThis feature is the same as SLC Device Locator, except you can locate u
Testing and Troubleshooting151295 10-510.3.3 I/O Point ControlThis feature allows you to toggle any output on or off and trip any input device. This c
Model 5700 Installation and Operation Manual1-6 151295Requirements and recommendations for proper use of fire alarm systems in-cluding smoke detectors
Model 5700 Installation and Operation Manual10-6 151295
151295 11-1Section 11Installation RecordsThis section of the manual is for you to use if you wish to track of how points, zones, and groups have been
Model 5700 Installation and Operation Manual11-2 151295
151295 A-1Appendix ACompatible DevicesA.1 Notification AppliancesFor proper operation, you must use polarized devices with a Model 7628 4.7k ohm EOL r
Model 5700 Installation and Operation ManualA-2 151295Faraday(cont.)2824 Horn Strobe5333 Multi-Tone Horn)5336 Multi-Tone Horn/Strobe 5337 Multi-Tone
Compatible Devices151295 A-3Faraday(cont.)6301 Mini-Horn 6302 Mini-Horn6310 Mini-Horn/Strobe6311 Mini-Horn/Strobe6312 Mini-Horn/Strobe6314 Series -M,
Model 5700 Installation and Operation ManualA-4 151295FCI(cont.)S2430W-FC StrobeS2430K-FC StrobeS2475-FC StrobeS2475W-FC StrobeS2475K-FC StrobeS24110-
Compatible Devices151295 A-5Gentex(cont.)GES-24-30 StrobesGES-24-60 StrobesGES-24-75 StrobesGES-24-110 StrobesGES-24-15/75 StrobesGES-24-177
Model 5700 Installation and Operation ManualA-6 151295System Sensor (cont.)P1224MC Horn/StrobeP1224MCK Horn/StrobeP1224MCP Horn/StrobeP1215 Ho
Compatible Devices151295 A-7System Sensor (cont.)PC2430W Horn/StrobePC2475 Horn/StrobePC2475W Horn/StrobePC2495 Horn/StrobePC2495W Horn/Stro
151295 2-1Section 2Agency Listings, Approvals, and RequirementsInstall and maintain in accordance with NFPA 72. Detector spacing shall be in accordanc
Model 5700 Installation and Operation ManualA-8 151295System Sensor (cont.)SC241575 StrobeSC241575W StrobeSC241575P StrobeSC241575PW StrobeSC2
Compatible Devices151295 A-9Wheelock(cont.)AMT-24MCW Horn/StrobeAH-24WP-R HornAMT-12\24-R Strobe HornAMT-24-LS-VFR Strobe HornAMT-24-LSM-VFR Strobe
Model 5700 Installation and Operation ManualA-10 151295Wheelock(cont.)NS-241575W Horn/StrobeNS-24MCW Horn/StrobeRSS-121575W StrobeRSS-241575W
Compatible Devices151295 A-11Wheelock(cont.)EH-DL1-R Electronic HornEH-EL1-R Electronic Horn Electronic HornEHS-DL1-W-VF-R Strobe Horn (single input)E
Model 5700 Installation and Operation ManualA-12 151295Wheelock(cont.)MIZ-24-WH-VF-W Mini-Horn/StrobeMIZ-24-WM-VF-W Mini-Horn/StrobeMT-12/24-R Strobe
Compatible Devices151295 A-13A.2 Door Holder DeviceThe following UL listed door holder can be used with the control panel: ESL DHS-1224.Wheelock(cont.
Model 5700 Installation and Operation ManualA-14 151295A.3 Two-Wire Smoke DetectorsTable A-2 lists two-wire smoke detectors that are compatible with t
Compatible Devices151295 A-15Falcon525 FDT1 N/A 17 / loop525T FDT1 N/A 17 / loopHochikiSIH-24F (HS-224D OR HSD-224) HD-3 HB-5 25 / loopSLK-24F (HS-224
Model 5700 Installation and Operation ManualA-16 151295
151295 B-1Appendix BSpecial Characters ListsThis section contains tables of programmable characters that may be used for device, module, and zone name
Model 5700 Installation and Operation Manual2-2 1512957. The telephone company may make changes in its facilities, equipment, operations, or pro-cedur
Model 5700 Installation and Operation ManualB-2 151295
Silent Knight Fire Product Warranty and Return PolicyGeneral Terms and Conditions• All new fire products manufactured by Silent Knight have a limited
• The defective board must be returned within 30 days of shipment of replacement board for customer to receive credit. No credit will be issued if the
Cut Along the Dotted LineModel 5700 Basic Operating InstructionsThese Instructions must be framed and displayed next to the 5700 panel in accordance w
Cut Along the Dotted Line
7550 Meridian CircleMaple Grove, MN 55369-4927763-493-64551-800-328-0103Fax: 763-493-6475© 2006 Silent Knight
Agency Listings, Approvals, and Requirements151295 2-3j) If your home has specially wired alarm equipment connected to the telephone line, ensure the
Model 5700 Installation and Operation Manual2-4 1512952.2.2 Requirements for Central Station Fire Alarm Systems1. Use both phone lines. Enable phone l
151295 3-1Section 3Before You Begin InstallingThis section of the manual is intended to help you plan your tasks to facilitate a smooth installation.
Model 5700 Installation and Operation Manual3-2 1512953.3 Electrical SpecificationsTable 3-1 list the terminal block on the 5700 as well as a descript
Before You Begin Installing151295 3-33.4 Wiring SpecificationsInduced noise (transfer of electrical energy from one wire to another) can interfere wit
Model 5700 Installation and Operation Manual3-4 1512953.5 Board Assembly DiagramFigure 3-2 Model 5700 AssemblyFigure 3-2 shows the circuit boards, an
Before You Begin Installing151295 3-53.6 Calculating Current Draw and Standby BatteryThis section is for helping you determine the current draw and st
Model 5700 Installation and Operation Manual3-6 1512953.6.1.1 Current Draw Worksheet for SLC DevicesUse Table 3-2 to determine current requirements du
Before You Begin Installing151295 3-71. Total does not include isolator devices or accessory bases.2. If using 24 VDC aux power only. No standby or al
Model 5700 Installation and Operation Manual3-8 1512953.6.1.2 Maximum Battery Standby LoadThe table below shows the maximum battery standby load for t
151295 4-1Section 4Control Panel Installation4.1 Mounting the Control Panel CabinetRead the environmental specifications in Section 3.2 before mountin
Installation ProcedureAdherence to the following will aid in problem-free installation with long-term reliability:Installation Precautions - Adherenc
Model 5700 Installation and Operation Manual4-2 1512954.1.3.1 Installing the Dead FrontFollow these steps to properly install the dead front panel int
Control Panel Installation151295 4-34.2 AC ConnectionAt installation, connect the AC terminals to the power source as shown in Figure 4-2. It may be n
Model 5700 Installation and Operation Manual4-4 1512954.3 Battery ConnectionThe control panel battery charge capacity is 7.0 to 35 AH. The main contro
Control Panel Installation151295 4-54.3.1 RBB Accessory CabinetThe Model RBB Accessory cabinet can be used when your backup batteries requirements use
Model 5700 Installation and Operation Manual4-6 1512953. Run extended battery cable from control panel cabinet through conduit to RBB cabinet. See Fig
Control Panel Installation151295 4-74.4 SBUS WiringThis section contains information on calculating SBUS wire distances and the types of wiring config
Model 5700 Installation and Operation Manual4-8 151295These cases are marked in the chart with an asterisk (*). Maximum length can never be more than
Control Panel Installation151295 4-9Wiring Distance calculation example:Suppose a system is configured with the following SBUS modules:2 - Module 5860
Model 5700 Installation and Operation Manual4-10 1512954.4.2 Wiring ConfigurationsFigure 4-8 illustrates Class B configuration.Figure 4-8 SBUS Class
Control Panel Installation151295 4-114.5 Remote Annunciator 5860 InstallationThe optional Model 5860 Remote Annunciator, shown in Figure 4-10, perform
While installing a fire alarm system may make lower insurance rates possible, it is not a substitute for fire insurance! An automatic fire alarm syst
Model 5700 Installation and Operation Manual4-12 1512954.5.1 Mounting the 5860This section of the manual describes mounting the remote annunciator. Th
Control Panel Installation151295 4-13The 5860 comes from the factory fully assembled. You must disassemble it for mounting. To disassemble the annunci
Model 5700 Installation and Operation Manual4-14 151295Flush Mounting with an Electrical BoxThe 5860 annunciator can be used with the following types
Control Panel Installation151295 4-154. After the annunciator wiring to the panel has been completed (described in Section 4.5.2), replace the electro
Model 5700 Installation and Operation Manual4-16 1512954.5.2 Model 5860 Connection to the PanelConnect the 5860 to the panel as shown in Figure 4-15.F
Control Panel Installation151295 4-175. Connect a printer to the 5824 as shown in Figure 4-17. Figure 4-16 5824 Connection to the PanelFigure 4-17 P
Model 5700 Installation and Operation Manual4-18 1512954.6.1 Selecting 5824 OptionsConfiguring the 5824 includes the following steps:• Add the module
Control Panel Installation151295 4-194.7 5880 LED Driver ModuleThe 5880 is an LED driver board that can be used in a wide variety of applications, inc
Model 5700 Installation and Operation Manual4-20 1512954.7.2 FACP ConnectionThe 5880 connects to the panel via the SBUS. Make connections as shown in
Control Panel Installation151295 4-214.7.3 LED WiringThere are four 12-pin connectors on the 5880 board for connecting LEDs. Each LED gets its power f
151295 iContentsSection 1Introduction ...
Model 5700 Installation and Operation Manual4-22 1512954.7.4 Dry Contact WiringThe 8 input circuits on the 5880 board are for monitoring switch inputs
Control Panel Installation151295 4-234.8 5865-3 / 5865-4 LED Annunciator InstallationThe 5865-3 and 5865-4 are LED annunciators. The 5865-4 has 30 map
Model 5700 Installation and Operation Manual4-24 1512954.8.2 5865 MountingMount the 5865-4 to a standard 4-gang electrical box. Mount the 5865-3 to a
Control Panel Installation151295 4-254.9 Configuring ModulesThis section describes how to configure any system hardware modules that have been added t
Model 5700 Installation and Operation Manual4-26 1512954.10 Telephone ConnectionConnect the telephone lines as shown in Figure 4-28. The Model 7860 ph
Control Panel Installation151295 4-274.12 Notification Appliance/Auxiliary Power CircuitsTwo outputs are built-in to the 5700 FACP which can be progra
Model 5700 Installation and Operation Manual4-28 1512954.12.1.2 Class A Notification WiringYou must use an appliance from the list of compatible appli
Control Panel Installation151295 4-294.12.2 Auxiliary Power InstallationNAC Circuits 1and 2 on the control panel can be used as auxiliary power circui
Model 5700 Installation and Operation Manual4-30 1512954.12.2.2 Constant PowerUse constant power for applications that require a constant auxiliary po
Control Panel Installation151295 4-314.14 Remote Station Applications4.14.1 Keltron Model 3158 InstallationThe control panel is compatible with Keltro
Model 5700 Installation and Operation Manualii 151295Section 4Control Panel Installation ...
Model 5700 Installation and Operation Manual4-32 1512954.14.2 City Box Connection Using the 5220 ModuleThis section describes how to connect the contr
Control Panel Installation151295 4-334.14.3 NFPA 72 Polarity Reversal4.14.3.1 Using the 5220 ModuleWhen the 5220 is wired and programmed for polarity
Model 5700 Installation and Operation Manual4-34 1512955. If necessary, adjust loop current using the potentiometer (R10) on the 5220 board . Normal l
Control Panel Installation151295 4-354.14.3.2 Using the 7644 ModuleWhen the 7644 is used for polarity reversal, it allows alarm and trouble events to
Model 5700 Installation and Operation Manual4-36 1512954.14.4 Using the SD500-ARM Addressable Relay ModuleWhen the SD500-ARM is wired for polarity rev
Control Panel Installation151295 4-374.14.5 Using a MR-201/T Control Relay From Air ProductsWhen the MR-201/T control relay is wired for polarity reve
Model 5700 Installation and Operation Manual4-38 1512954.14.6 Transmitter Activated by Dry ContactsThis section describes the connection of a UL 864 l
151295 5-1Section 5SLC Device InstallationCaution!To avoid the risk of electrical shock and damage to the unit, power should be OFF at the control pan
Model 5700 Installation and Operation Manual5-2 1512955.2 Maximum Number of DevicesThe 5700 supports 50 addressable devices.5.3 Wiring Requirements fo
SLC Device Installation151295 5-3Figure 5-1 and Figure 5-2 show how wire length is determined for out-and-back tap and T-tap style wiring.
Contents151295 iii4.14.6 Transmitter Activated by Dry Contacts ...
Model 5700 Installation and Operation Manual5-4 1512955.3.2 Wiring 5815XL in Style 6 & 7 (Class A) ConfigurationFigure 5-3 illustrates how to wire
SLC Device Installation151295 5-55.4 Wiring DetectorsThe information in this section applies to the following models: SD505-AHS Heat Detector, SD505-A
Model 5700 Installation and Operation Manual5-6 1512955.5 Addressing DevicesThis section tells how to address detectors and modules.5.5.1 SD505-APS, S
SLC Device Installation151295 5-75.5.2 SLC Devices with Dip SwitchesInput and relay module addresses are set using the dip switches on the module boar
Model 5700 Installation and Operation Manual5-8 151295
151295 6-1Section 6Programming OverviewThis section of the manual is intended to give you an overview of the programming process. Please read this sec
Model 5700 Installation and Operation Manual6-2 1512956.1.1 Input Points JumpStart will determine the number and type of input points (detectors or co
Programming Overview151295 6-35. When the message "Configuring System Done" displays, press any key to continue.6. Select one of the followi
Model 5700 Installation and Operation Manual6-4 1512956.2 Mapping OverviewThis section of the manual is an overview of mapping. Details about how to s
Programming Overview151295 6-56.2.1 Input Point MappingInput points are assigned to input zones. Any input point can be assigned to any input zone. (I
Model 5700 Installation and Operation Manualiv 1512957.3.1.4 Cadence Patterns ...
Model 5700 Installation and Operation Manual6-6 1512956.2.2 Output Circuit MappingFigure 6-3 is a simple example showing how to assign notification an
Programming Overview151295 6-76.2.3 Zone Event Mapping There are 8 types of events that can occur in zones (see below). For each event type, you can a
Model 5700 Installation and Operation Manual6-8 151295Figure 6-5 Example of Zone Events Mapped to Output Groups and Patterns
Programming Overview151295 6-96.2.4 Mapping LED PointsFigure 6-6 is a simple example showing how LED points are mapped to zones and output groups. Typ
Model 5700 Installation and Operation Manual6-10 1512956.3 Programming Using the 5660 Silent Knight Software SuiteYou can use the 5660 Silent Knight S
Programming Overview151295 6-116.4.1 Entering / Exiting the Program MenuTo enter the Program Mode: 1. Press or to display the main menu.2. Enter t
Model 5700 Installation and Operation Manual6-12 1512956.4.3 Selecting Options and Entering DataThere are several ways to make programming selections
Programming Overview151295 6-136.5 Programming Menu Quick ReferenceThis section of the manual lists all Program Menu options in the order they appear
Model 5700 Installation and Operation Manual6-14 151295Group1Edit Group Select GroupGroup NameEnter Name1Section 7.4.1.1Enter Number1Enter Name2Enter
Programming Overview151295 6-15Point(cont.)SLC Loop(cont.)Enter PtSWITCHMAN_PULLSection 7.5WAT ER F LO WLATCHNLATCHSUPERVSY LATCHNLATCHFIREDRILLSILENC
Contents151295 vSection 8System Operation ...
Model 5700 Installation and Operation Manual6-16 151295System OptionsReporting AccountsEdit Acct.For each account (1-4), select:Edit Account # *123456
Programming Overview151295 6-17System Options (cont.)System Event OutputsTrouble EventsSystem TroubleSelect GroupNone selectedSection 7.6.3.1Select Ca
Model 5700 Installation and Operation Manual6-18 1512951. Use of multiple notification groups may not synchronize with each other.JumpStart AutoPrgNo
151295 7-1Section 7ProgrammingThis section of the manual describes how to manually program the control panel from the built-in annunciator. Each subse
Model 5700 Installation and Operation Manual7-2 1512957.2 ModulesThis section lists the options available under the module option in the program menu.
Programming151295 7-37.2.1.2 Module, Wiring Class8. Choose the class of wiring you wish to use for this module by pressing the or arrow, then pres
Model 5700 Installation and Operation Manual7-4 1512957.3 ZoneThrough the zone option in the program menu you can edit, add, delete, and view zone poi
Programming151295 7-58. Select the characters for the zone name by pressing the or arrow until the desired character is shown then press .OREnter
Model 5700 Installation and Operation Manual7-6 151295Alarm Delay Characteristics3. Select the alarm delay characteristics by pressing the or arro
Programming151295 7-7Heat Temperature SettingUse this feature to set the temperature at which heat detectors will respond. The range is 135° to 150° F
Kommentare zu diesen Handbüchern