Distributed Power ModulePart Number 151253F, 08/03SILENT KNIGHT5499Installation Manual
InstallationP/N 151253 74.2 Wire RoutingTo avoid induced noise (transfer of electrical energy from one wire to another), keep input wiring isolated fr
Model 5499 Distributed Power Module Installation Manual8 P/N 1512534.3 Current Requirements (Standby and Alarm)4.3.1 Current Drawn From Host Panel Tab
InstallationP/N 151253 9Table 4-2: Battery Calculation WorksheetDeviceNumber of DevicesCurrent per DeviceStandby CurrentAlarm CurrentFor each device u
Model 5499 Distributed Power Module Installation Manual10 P/N 1512534.4 Layout of the 5499 to a Control PanelFigure 4-2 shows the general layout of th
InstallationP/N 151253 114.5 Trouble Relay The 5499 has a Form C trouble relay built into Terminals 11-13. The relay provides a normally open and a no
Model 5499 Distributed Power Module Installation Manual12 P/N 151253• When wiring to terminal 18 on the 5499, you must use two separate wires. Do not
InstallationP/N 151253 13Class B Supervised Input CircuitsFigure 4-5 shows Class B supervised wiring from a fire alarm control panel to the Model 5499
Model 5499 Distributed Power Module Installation Manual14 P/N 1512534.8 AC ConnectionWire AC power as shown in Figure 4-6.Figure 4-6 120 VAC Connecti
InstallationP/N 151253 154.10 DIP Switch SettingsA 7-position DIP switch on the 5499 board allows you to select the following:• How long the 5499 will
Model 5499 Distributed Power Module Installation Manual16 P/N 151253Figure 4-9 Setting DIP Switches 1-3 (Continued)Special Note for Input/Output Conf
P/N 151253 iContentSection 1Introduction ...
InstallationP/N 151253 174.10.2 Selecting Synchronized Input/Output ConfigurationsThe following sections describe how to configure the 5499 as a synch
Model 5499 Distributed Power Module Installation Manual18 P/N 1512534.10.2.3 Selecting Synchronized System Sensor ConfigurationsTo select the input/ou
InstallationP/N 151253 194.10.3 Setting the Loss of AC DelayNormal selection for reporting loss of AC is 6 hours.The ON position is for test purposes
Model 5499 Distributed Power Module Installation Manual20 P/N 151253Section 5Connection to Silent Knight PanelsThe drawings in this section show you h
Connection to Silent Knight PanelsP/N 151253 21Figure 5-3 Connection to 5204 Fire Control/CommunicatorFigure 5-4 Connection to 5207 Fire Control/Com
Model 5499 Distributed Power Module Installation Manual22 P/N 151253 Figure 5-5 Connection to the SK-2224 Fire Alarm Control PanelFigure 5-6 Conn
Connection to Silent Knight PanelsP/N 151253 23Figure 5-7 Connection to the SK-6324 Fire Alarm Control Panel
Model 5499 Distributed Power Module Installation Manual24 P/N 151253Section 6Sample ApplicationsThe drawings in this section show various 5499 configu
Sample ApplicationsP/N 151253 25Note:When multiple power supplies are used with one control unit they will not sync with each other.Figure 6-3 One Co
Model 5499 Distributed Power Module Installation Manual26 P/N 151253Figure 6-5 Each Control Activates Five Notification Appliance Circuits6.2 Non-Res
Model 5499 Distributed Power Module Installation Manualii P/N 151253Section 5Connection to Silent Knight Panels ...
Sample ApplicationsP/N 151253 276.3 Door Holder ApplicationIn a typical door holder application, the door holder power must be interrupted to close al
Model 5499 Distributed Power Module Installation Manual28 P/N 151253Section 7TroubleshootingLight-emitting diodes (LEDs) indicate fault conditions. T
TroubleshootingP/N 151253 297.2 Trouble ConditionsNote:While Input 1 & 2 are activated, Input 1 & 2 will not open to indicate a trouble or sup
Model 5499 Distributed Power Module Installation Manual30 P/N 1512537.3 Removing and Replacing the Control PanelThis section of the manual provides in
P/N 151253 A-1Appendix AUL Listed Notification AppliancesFor proper operation, use polarized devices with a Model 7628 4.7k ohm EOL resistor on each c
Model 5499 Distributed Power Module Installation ManualA-2 P/N 151253Faraday(Cont.)5386 8-Tone Horn/Strobe with Sync Strobe5387 8-Tone Horn/Strobe
P/N 151253 A-3FCI130-3117C Mini Horn130-3147C Mini HornBLV-6 Vibrating BellBLV-10 Vibrating BellBLVCH Vibrating ChimeH12/24-FC HornH12/24W-FC HornH12/
Model 5499 Distributed Power Module Installation ManualA-4 P/N 151253Federal Signal450 HornVALS Horn/StrobeGentexGX90-4 HornGXS-4-15-1 StrobeGXS-4-1
P/N 151253 A-5System Sensor (Cont.)PS2475ADA Mini-Horn/StrobeMDL Sync. ModuleMDLW Sync. ModuleWheelock46T-G4-24-R Bell46T-G6-24-R Bell46T-G10-24-R B
Model 5499 Distributed Power Module Installation ManualA-6 P/N 151253Wheelock(Cont.)CF-BF1-R ChimeCH-CF1 ChimeCH-CF1-R ChimeCH-CF1-W ChimeCH-DF1 Chime
P/N 151253 1Section 1IntroductionThe Model 5499 is a notification and auxiliary power expander that provides up to 9 amps of filtered, 24 volt power f
P/N 151253 A-7Wheelock(Cont.)IS1-24-VFR Remote StrobeIS3-24-VFR Remote StrobeISP-24-HFR Remote StrobeLS-24-VFR Remote StrobeLS1-24-VFR Remote StrobeLS
Model 5499 Distributed Power Module Installation ManualA-8 P/N 151253Wheelock(Cont.)NS-24MCM-FR Horn StrobesNS-24MCW-FW Horn StrobesNS-2415W-FR
P/N 151253 A-9Wheelock(Cont.)SM-12/24-R Sync ModuleSR-2415-VFR Sync StrobeSRP-2415-HFR Sync StrobeSR-241575-VFR Sync StrobeSRP-241575-VFR Sync Str
Model 5499 Distributed Power Module Installation ManualA-10 P/N 151253
Silent Knight Fire Product Warranty and Return PolicyGeneral Terms and Conditions• All new fire products manufactured by Silent Knight have a limited
• A new or refurbished board will be shipped to the customer. The customer will initially be billed for the replacement board but a credit will be iss
© 2003 Silent KnightPart Number 151253F, 08/037550 Meridian CircleMaple Grove, MN 55369-4927612-493-64551-800-328-0103Fax: 612-493-6475
Model 5499 Distributed Power Module Installation Manual2 P/N 151253Section 2UL RequirementsWhen installed in accordance with NFPA 72 standards, the 54
System OverviewP/N 151253 3Section 3System Overview3.1 Terminal Descriptions and Electrical RatingsCAUTIONEach output circuit is rated at 3 amps. DO
Model 5499 Distributed Power Module Installation Manual4 P/N 1512533.2 Signal Input TerminalsTerminals 14 through 19 are polarized signal input termin
System OverviewP/N 151253 53.3 Notification Appliance Circuit TerminalsTerminals 3 through 10 are the NAC terminals. Each of the four outputs is rated
Model 5499 Distributed Power Module Installation Manual6 P/N 151253Section 4InstallationBefore installing the 5499, the AC input must first be wired i