Installation
P/N 151253 11
4.5 Trouble Relay
The 5499 has a Form C trouble relay built into Terminals 11-13. The relay provides a
normally open and a normally closed contact, both of which are rated at 2.5A. The trouble
relay will deactivate under any trouble condition.
A typical application of the trouble relay is to connect the 5499 normally closed (N.C.)
contacts in series with the EOL supplied with the fire alarm control panel. This will cause a
trouble on the fire panel when the 5499 opens its trouble contacts.
Note:The N.C. contact is the relay contact that is closed when the 5499 has power and there are no trouble con-
ditions.
Figure 4-3 Trouble Relay Connection Example
4.6 Input and Output Wiring
4.6.1 Class A Supervised Wiring
Figure 4-4 shows how to wire for Class A input and output supervision. Use in/out wiring
methods for proper supervision. (Refer to the Appendix for notification appliances compatible
with the 5499.)
Class A Output Notification Appliance Circuits
The configuration shown in Figure 4-4 shows two, 3-amp devices wired as Class A circuits.
When you are using the outputs as Class A circuits, loop the wiring back to the corresponding
circuit pair. For Class A wiring, no external EOL is necessary since it is built into the 5499
board.
Class A Supervised Input Circuits
The configuration shown in Figure 4-4 shows Class A supervised wiring from a fire alarm
control panel to the 5499 board. Pay close attention to the polarities when wiring a panel to the
5499 and follow these requirements:
Must be connected to
a power limited source