Model 5499 Distributed Power Module Installation Manual
4 P/N 151253
3.2 Signal Input Terminals
Terminals 14 through 19 are polarized signal input terminals. They provide the signaling
connection from the main panel to the 5499. See Figure 4-2 for more details.
Section 5 shows connections to specific Silent Knight fire alarm control units.
The main panel supervises its notification appliance circuits used for communicating with the
5499 the same way it supervises ordinary notification appliance circuits. The signal inputs on
the 5499 monitor the polarity of the voltage coming from the main panel’s notification
appliance circuits to determine when to operate the notification appliance circuits on the 5499.
The 5499 emulates the trouble behavior of a normal notification appliance circuits by
breaking the EOL supervision current for internal or output trouble conditions on the 5499.
Note that the 5499 will accurately sense the polarity of the main panel’s notification appliance
circuits to drive the outputs whether or not the supervision connection is intact. The following
situations will disconnect the EOL supervision at the signal inputs and indicate a trouble
condition:
Low AC power
Low Battery condition
Earth ground fault to the system power or system ground
Auxiliary output power-limited condition
EOL supervision trouble or power-limited condition at an output
Trouble conditions will not necessarily occur for both inputs when the trouble is specific to a
particular output. Only the signal input controlling the output circuit that is in trouble will
indicate a trouble condition. Below are examples where both inputs do NOT indicate trouble
for a trouble occurring at only one output circuit.
Note:Once the inputs are driven with forward polarity to activate the outputs, the main control panel will not be
able to sense trouble conditions through its notification appliance circuits connected to the 5499 input cir-
cuits. Use the 5499 trouble relay when it is necessary to monitor trouble conditions and active alarm con-
ditions at the same time.
Section 7 explains the significance of each trouble condition in more detail.
Example 1: If input 1 controls all four outputs, a fault on any output will cause input 1
to indicate trouble. The fault does not affect input 2.
Example 2: If input 1 controls outputs 1 and 2, and input 2 controls outputs 3 and 4, a
fault condition on output 3 or 4 will cause input 2 to indicate trouble. The
fault does not affect input 1.