Section 1
Introduction
The Model 5499 is a notification and auxiliary power expander that provides up to 9 amps of
filtered, 24 volt power for powering notification appliances and auxiliary devices. The 5499
provides its own AC power connection, battery charging circuit, and battery connections.
Used with security and fire panels, the 5499 enables you to connect and distribute power to
many more devices than your panel may normally allow.
Input Configurations
The 5499 has two optically isolated signaling inputs that provide the signal connection
from the main control panel to the 5499 (see Section 3.2 for more details).
Output Configurations
The 5499 has four power-limited notification appliance circuits that can be configured in
various combinations of Class A and Class B circuits (see Section 3.3 for more details).
Auxiliary Power Configurations
The 5499 has a dedicated, power-limited, auxiliary output that can be configured in two
different ways. The auxiliary output can either be non-resettable (always on), or
configured to switch off when the AC power goes off to conserve the battery standby
power. When the auxiliary power is configured to switch off, there is a 30 second delay
before the auxiliary power is turned off after the AC power goes off (see Section 4.10.4 for
more details).
Form C Trouble Relay
The 5499 includes a general trouble relay that will de-energize for any trouble situation on
the 5499 (see Section 4.5 for more details).
Earth Fault Detection
The 5499 monitors for earth faults to the system power or system ground. When detected,
the system de-energizes the trouble relay and the input supervision relays (see Section 6.2
for details).
ANSI Temporal Code
The 5499 provides two configuration options that will drive outputs with the ANSI
temporal code if the inputs are on constant (see Section 4.10.1 for details).
Supports Synchronization appliances
The 5499 provides configuration options that will eliminate the need for sychronization
modules when using AMSECO, Faraday, Gentex, System Sensor or Wheelock sync
appliances.